eleven quick, simple fixes to increase sag immunity |
|
|
Here are eleven quick, simple fixes that will increase voltage sag immunity. Of course, like every engineering change, there are tradeoffs that you will need to consider as you're selecting a solution.
|
|
| 1. Find and fix the problem. Yes, it's an obvious suggestion. But it's the best place to start. Figure out exactly what is causing the problem with a sag generator equipped with a good data acquisition system. Once you know what the problem is (if you even have a sag problem!), it will be much easier to fix. Tradeoff: Takes time and money; if you're a good at guessing, you might skip this step. | |
| 2. Add a power quality relay. These small, simple devices detect voltage sags, and give you a simple relay contact when a sag occurs. The best ones (such as PSL's PQ1 also detect other disturbances, such as high frequency impulses and voltage swells. Your system can then adjust its behavior whenever a voltage sag occurs - for example, by resetting some of its components. Tradeoff: Can require some simple reprogramming of your system. |
![]() The best solutions are the simplest. Add an inexpensive power quality relay to your system, then adjust your software so it corrects any problems whenever a power disturbance occurs. |
| 3. Switch power supply settings. Many power supplies can be set to accomodate different voltage ranges, and these ranges often overlap. Choose a range where your nominal voltage is near the top of the range, and you'll have more room for voltage sags. For example, if your power supply has Range #1, 95V-250V (accomodating Japan and Europe), and Range #2, 110V-270V (accomodating North America and Australia), and you have a 240V nominal voltage, you will have greater sag immunity on Range #1. Tradeoff: Less margin at the top end against voltage swells. | |
| 4. Connect your single-phase power supply phase-to-phase. If you can stay within your power supply's acceptable voltage range, and if you have three-phase power available, you can get a quick 70% boost in available voltage by connecting phase-to-phase. For example, if your power supply is rated as 90V-250V, and you are using it on a 120V circuit, you can only tolerate a sag to 75%. But if you connect it phase-to-phase, the nominal voltage will be 208V and you will be able to tolerate a sag to 45%. Tradeoffs: Less margin for voltage swells; sometimes inconvenient; sensitive to sags on two phases, instead of just one. | |
| 5. Reduce the load on your power supply. Lightly loaded power supplies always tolerate voltage sags better than heavily loaded power supplies. If you can determine that a particular power supply is causing your equipment to mis-operate during a voltage sag, consider moving some of its loads to another power supply. Tradeoffs: May be inconvenient to install; carefully consider effects of a shut-down on one of the power supplies. | |
| 6. Increase the rating of your power supply. If you can't move the loads, use a bigger supply for the same load -- relative to its rating, it will be more lightly loaded. Tradeoffs: cost and size tend to go up; there may not be room for a larger power supply. | |
| 7. Use a three-phase power supply instead of a single-phase supply. A properly-designed (and lightly loaded) three-phase power supply will effectively tolerate voltage sags on one or two phases that would shut down a single-phase power supply. Trade-off: Cost and size are larger; requires three-phase circuit breakers, shut-down circuits. | |
| 8. Run your power supply from a DC bus. Sometimes you can substitute a DC-operated power supply for an AC-sourced supply. If it does nothing else, this will narrow down your problems to supporting a DC bus, which can often be done with simple capacitors or batteries. (This is the approach that high-reliability telecommunications systems take, using a 48 Vdc supply as their power distribution system.) Trade-offs: protective devices (fuses, circuit breakers, etc.) need to be changed or rated for DC; may not be convenient. |
![]() The telecommunications industry operates equipment from a 48Vdc bus, making systems virtually immune to voltage sags and power interruptions -- the ac power system is only used to charge the batteries. |
| 9. Change the trip settings. If you can identify an unbalance relay, an undervoltage relay, or an internal reset or protection circuit that is inadvertently tripping during a voltage sag, change its settings. Consider changing the threshold, and consider changing the trip delay; either or both might make sense. Sometimes this can be as simple as twisting a knob; sometimes it may take a component change or firmware adjustment. You can only use this solution when the trip settings were set too conservatively to begin with; trips are useful and important, so you don't want to eliminate them completely. Trade-offs: someone chose those set-points for a reason, so you don't want to change them arbitrarily; changing components and/or firmware can create service and repair problems later on. | |
| 10. Slow the relay down. If the equipment is misoperating because a relay in the EMO circuit is operating too quickly, consider slowing it down. You might use a relay with more mechanical mass (such as a contactor), or you might use a relay hold-in accessory. Trade-offs: possibly more complexity on the EMO circuit; you don't want to slow the EMO circuit down so much that it becomes unsafe. |
![]() You can add a simple "hold-in" device across the coil of a relay or contactor to increase its sag immunity. Suppliers include Power Quality Solutions, among others. |
| 11. Get rid of the voltage sag itself. As a last resort, consider installing a quick-operating voltage regulator on your AC supply. There are a variety of technologies: ferroresonant transformers, solid-state voltage compensation, etc. But make sure that you aren't making the problem worse; if the original cause of the voltage sag is downstream from your voltage sag regulator, the voltage sags will actually get deeper and longer when you install the fix. Tradeoffs: size and cost. |
![]() For larger three-phase applications, the Dynamic Sag Corrector from Soft Switching Technologies can eliminate the sag itself. |
|
Sag sensitivity - Five ways equipment fails during voltage sags CBEMA curve - voltage sag depth and duration at world-wide semiconductor plants Sag sources - The sources of voltage sags Semiconductor sag standards - Industry standards F47, F42 Alex McEachern, 8/2001 |
|